Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-09-6 
 
09-46 
CANopen Master Address 
 
 
   
 Default: 100 
 
 
Settings 0–127 
 
 
09-49 
CANopen Extension Setting 
 
 
   
 Default: 0002h 
 
 
Settings  bit0: Index 604F and 6050 update to the 1
st
 acceleration / deceleration time or 
not.  
bit0 = 0: update to the 1
st
 acceleration / deceleration time (default)   
bit0 = 1: do not update 
bit1: The verification of CANopen identification code is distinguished by power 
module or drive series. 
bit1 = 0: distinguished by power module 
bit1 = 1: distinguished by drive series 
 bit0=0, control the first acceleration time (Pr.01-12) and the first deceleration time (Pr.01-13) 
directly via CANopen.   
Each series of the drive and each power module of drive have its own EDS file and this is more 
cumbersome and unmanageable. Therefore, using Pr.09-49 bit1=1 CANopen identification code 
verification distinguished by drive series and which means the C2000 series requires only one 
EDS file. 
 
09-60 
Communication Card Identification 
 
 
   
  Default: Read only 
 
 
Settings 
0: No communication card 
1: DeviceNet Slave 
2: Profibus-DP Slave 
3: CANopen Slave / Master 
5: EtherNet / IP Slave 
6: EtherCAT (applied to 230V / 460V models) 
12: PROFINET (applied to 230V / 460V models) 
 
 
09-61 
Firmware Version of Communication Card 
 
 
   
  Default: Read only 
 
 
Settings Read only 
 
 
09-62 
Product Code 
 
 
   
  Default: Read only 
 
 
Settings Read only 
 
 
09-63 
Error Code 
 
 
   
  Default: Read only 
 
 
Settings Read only