Chapter 14 Fault Codes and DescriptionsC2000  Plus 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
17 
 
Over-heat key 
components (oH2) 
The drive has detected the key components are 
heat 
Action and Reset 
Action condition  Refer to the table below for oH2 level of each models 
Action time 
The oH2 fault occurs when the temperature 
sensor of key components detects 
the temperature is higher than the protection condition for 1 second. 
Fault treatment parameter  N/A 
Reset method  Manual reset 
Reset condition 
The drive auto-resets when the temperature sensor of key components 
the temperature is lower than oH2 error level minus (–) 10°C 
Record  Yes 
Cause  Corrective Actions 
Check if the ambient temperature 
or temperature inside the control 
cabinet is too high, or if there is 
obstruction in the ventilation hole 
of the control cabinet. 
1.  Check ambient temperature. 
2.  Regularly inspect the ventilation hole of the control cabinet. 
3. 
Change the installed place if there are heating objects, such as braking 
resistors, in the surroundings. 
4. 
Install/ add cooling fan or air conditioner to lower the temperature inside the 
cabinet. 
Check if there is any obstruction 
on the heat sink or if the fan is 
running. 
Remove the obstruction or replace the cooling fan. 
Insufficient ventilation space  Increase ventilation space of the drive. 
Check if the drive matches the 
corresponding load 
1.  Reduce the load 
2.  Reduce the carrier 
3.  Replace the drive with a larger capacity model. 
The drive has run 100% or more 
than 100% of the rated output for a 
long time 
Replace the drive with a larger capacity model. 
Unstable power  Install reactor(s) 
Load changes frequently  Reduce load changes 
 
oH1/ oH2 warning level 
Model  oH1  oH2 
oH warning 
oH1 warning = (Pr.06-15) 
110 
95 
oH1 Warning = oH1 – 5 
oH2 Warning = oH2 – 5 
80