Chapter 14 Fault Codes and DescriptionsC2000  Plus 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
48 
 
ACI loss   
(ACE) 
Analog input loss (including all the 4–20mA analog 
signal) 
Action and Reset 
Action condition  When the analog input is < 4mA (only detects 4–20mA analog input) 
Action time  Act immediately 
Fault treatment parameter 
Pr.03-19 
0: Disable 
1
: Continue operation at the last frequency (warning, ANL is displayed on the 
keypad) 
2: Decelerate to stop (warning, ANL is displayed on the keypad) 
3: Stop immediately and display ACE 
Reset method 
Auto 
When Pr.03-19 = 1 or 2, ACE is a “Warning”. When ana
is > 4mA, the warning is automatically cleared. 
Manual  When Pr.03-19 = 3, ACE is a “Fault”. You must reset manually. 
Reset condition  Reset immediately 
Record  When Pr.03-19 = 3, ACE is a “Fault”, and the fault is recorded. 
Cause  Corrective Actions 
ACI cable is loose or cut off 
Tighten the terminal. 
Replace the cable with a new one. 
External device failure  Replace the device with a new one. 
Hardware failure  Check all the wiring. If ACE still occurs, return to the factory for repair.