Chapter 14 Fault Codes and DescriptionsC2000  Plus 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
58 
 
Modbus transmission 
time-out   
(CE10) 
MODBUS transmission time-out occurs 
Action and Reset 
Action condition  When the communication time exceeds the detection time for Pr.09-03 time-out.
Action time  Pr.09-03 
Fault treatment parameter 
Pr.09-02 
0: Warn and continue operation 
1: Fault and ramp to stop 
2: Fault and coast to stop 
3: No warning and continue operation 
Reset method  Manual reset 
Reset condition  Reset immediately 
Record  Yes 
Cause  Corrective Actions 
The upper unit does not transmit 
the communication command 
within Pr.09-03 setting time. 
Check if the upper unit transmits the communication command within the 
time for Pr.09-03. 
Malfunction caused by 
interference 
Verify the wiring and grounding of the communication 
circuit. It is recommended 
to separate the communication circuit from the main circuit, or wire in 90 degree 
for effective anti-interference performance. 
Different communication setting 
from the upper unit 
Check if the setting for Pr.09-02 is the same as the setting for the upper unit. 
Disconnection or bad connection 
of the cable 
Check the cable and replace it if necessary.