Chapter 16 PLC Function ApplicationsMS300
712
API
MOV
S D
Move data
12
D
P
bit device
Word device
16-bit command (5 STEP)
MOV
Continuous
execution type
MOVP
Pulse
execution type
32-bit command (9 STEP)
DMOV
Continuous
execution type
DMOVP
Pulse
execution type
Flag signal: none
X
Y
M
K
H
KnX
KnY
KnM
T
C
D
S
D
Notes on operand usage: none
S: Data source. D: Destination of data movement.
Moves the content in S to D. When the command does not execute, the content
of D does not change.
When X0 = OFF, the content of D10 does not change; if X0 = ON, the value K10
is moved to data register D10.
When X1 = OFF, the content of D10 does not change; if X1 = ON, the current
value of T0 is moved to data register D10.
X0
K10MOV D0
X1
T0MOV D10