Chapter 11 Summary of Parameter SettingsMS300
234
Pr.
Explanation
Settings
Default
06-09
Over-Torque Detection
Selection (Motor 2)
0: No function
1: Continue operation after over-torque detection during
constant speed operation
2: Stop after over-torque detection during constant speed
operation
3: Continue operation after over-torque detection during
RUN
4: Stop after over-torque detection during RUN
0
06-10
Over-Torque Detection
Level (Motor 2)
10–250%
(100% corresponds to the rated current of the drive)
120
06-11
Over-Torque Detection
Time (Motor 2)
0.1–60.0 sec.
0.1
06-12
Current Limit
0–250%
(100% corresponds to the rated current of the drive)
150
06-13
Electronic Thermal Relay
Selection 1 (Motor 1)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disabled
2
06-14
Electronic Thermal Relay
Action Time 1 (Motor 1)
30.0–600.0 sec.
60.0
06-15
Temperature Level
Overheat (OH) Warning
0.0–110.0
o
C
Depending
on the
model
power
06-16
Stall Prevention Limit
Level
(Weak Magnetic Field
Current Stall Prevention
Level)
0–100% (refer to Pr.06-03–Pr.06-04)
100
06-17
Fault Record 1
0: No fault record
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during steady operation (ocn)
4: Ground fault (GFF)
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage during constant speed (Lvn)
14: Low-voltage at stop (LvS)
0
06-18
Fault Record 2
0
06-19
Fault Record 3
0
06-20
Fault Record 4
0
06-21
Fault Record 5
0
06-22
Fault Record 6
0
Fault Record 7 (Pr.14-70)
0
Fault Record 8 (Pr.14-71)
0
Fault Record 9 (Pr.14-72)
0
Fault Record 10 (Pr.14-73)
0