Chapter 12 Descriptions of Parameter SettingsMS300
287
Related parameters: Pr.01-00 Motor 1 Maximum Operation Frequency, Pr.01-11 Output
Frequency Lower Limit.
When the drive starts, it operates according to the V/F curve and accelerates from the minimum
output frequency (Pr.01-07) to the setting frequency. It is not limited by the lower output
frequency settings.
Use the frequency upper and lower limit settings to prevent operator misuse, overheating
caused by the motor’s operating at a too low frequency, or mechanical wear due to a too high
speed.
If the frequency upper limit setting is 50 Hz and the frequency setting is 60 Hz, the maximum
output frequency is 50 Hz.
If the frequency lower limit setting is 10 Hz and the minimum output frequency setting (Pr.01-07)
is 1.5 Hz, then the drive operates at 10 Hz when the Frequency command is higher than Pr.01-
07 but lower than 10 Hz. If the Frequency command is lower than Pr.01-07, the drive is in ready
status without output.
01-12
Acceleration Time 1
01-13
Deceleration Time 1
01-14
Acceleration Time 2
01-15
Deceleration Time 2
01-16
Acceleration Time 3
01-17
Deceleration Time 3
01-18
Acceleration Time 4
01-19
Deceleration Time 4
01-20
JOG Acceleration Time