Chapter 12 Descriptions of Parameter SettingsMS300
403
Parallel connection
Feedback Signal Detection Time
Valid only when the feedback signal is ACI (4–20 mA).
This parameter sets the detection time for abnormal PID signal feedback. You can also use it
when the system feedback signal response is extremely slow. (Setting the detection time to 0.0
disables the detection function.)
Feedback Signal Fault Treatment
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: Warn and operate at last frequency
Valid only when the feedback signal is ACI (4–20 mA).
Sets the treatments when the PID feedback signal is abnormal.
0.00–599.00 Hz / 0.00–200.00%
0.00–599.00 Hz / 0.00–200.00%
Determines the sleep frequency, and if the sleep time and the wake-up frequency are enabled or
disabled.
Pr.08-10 = 0: Disabled; Pr.08-10 ≠ 0: Enabled