Sets the resonance frequency of the mechanical system. Adjust it to a smaller value to suppress
the mechanical system resonance.
A larger value improves resonance suppression function.
The notch filter frequency is the mechanical frequency resonance.
FOCPG and FOC Sensorless mode:
The motor rated current = 100%. The settings for Pr.11-17–Pr.11-20 compare with the Pr.03-00 =
7, 8, 9, 10. The minimum value of the comparison result is the torque limit. The diagram below
illustrates the torque limit.
TQCPG and TQC sensorless mode:
The function of Pr.11-17–11-20 is the same as FOC; however, in this case, the torque limit and
the torque command executes the output torque limit at the same time. Therefore, the minimum
value between Pr.11-17–11-20 and Pr.06-12 becomes the current output torque limit.
Refer to Pr.11-34 for calculation equation for the motor rated torque.