Chapter 13 Warning CodesMS300
474
ID No.
Display on LCD Keypad
Warning Name
Description
2
Communication error 2
(CE2)
RS-485 Modbus illegal data address
Action and Reset
Action Condition
When the input data address is incorrect
Action Time
Immediately act
Warning Setting Parameter
N/A
Reset Method
“Warningoccurs when Pr.09-02 = 0 and the motor drive keeps running. The
drive resets automatically when receiving the correct data address.
Reset Condition
Immediately reset
Record
N/A
Cause
Corrective Actions
Incorrect communication
command from upper unit
Check if the communication command is correct.
Malfunction caused by
interference
Verify the wiring and grounding of the communication circuit. It is recommended
to separate the communication circuit from the main circuit, or wire in 90 degree
for effective anti-interference performance.
Different communication setting
from the upper unit
Check if the setting for Pr.09-04 is the same as the setting for the upper unit.
Disconnection or bad connection
of the cable
Check the cable and replace it if necessary.