Chapter 13 Warning CodesMS300
484
Warning Setting Parameter
Pr.06-73
0: No function
1: Fault and coast to stop
2: Fault and ramp to stop by the 2
nd
deceleration time
3: Warn and continue operation
“Warning” occurs when Pr.06-73 = 3. The “Warning” automatically
clears when the output current is larger than (Pr.06-71+0.1 A).
“Error” occurs when Pr.06-73 = 1 and 2. You must reset manually.
Does not record when Pr.06-73 = 3 and uC displays (“Warning”).
Exclude the connection issue of the motor and its load.
Improper setting for the low
current protection
Set the proper settings for Pr.06-71, Pr.06-72 and Pr.06-73.
Check the loading status.
Make sure the loading matches the motor capacity.