Chapter 14 Fault CodesMS300
561
Low-voltage at stop
(LvS)
1. DC bus voltage is lower than Pr.06-00 setting value
at stop
2. Hardware failure in voltage detection
Pr.06-00 (Default = depending on the model)
Immediately act when the DC bus voltage is lower than Pr.06-00
Fault Treatment Parameter
Manual / Auto:
230V series: Lv level + 30 V
DC
+ 500 ms
460V series: Lv level + 60 V
DC
+ 500 ms
575V series: Lv level + 75 V
DC
+ 500 ms
Improve power supply condition.
Check if the power specification matches the drive.
Adjust voltage to the power range of the drive.
Cycle the power after checking the power. If LvS error still exists, return to the
factory for repair.
Start up the motor with large
capacity
Check the power system.
Increase the capacity of power equipment.