EasyManuals Logo
Home>Delta>DC Drives>VFD1A5MS43ANSAA

Delta VFD1A5MS43ANSAA User Manual

Delta VFD1A5MS43ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #574 background imageLoading...
Page #574 background image
Chapter 14 Fault CodesMS300
565
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
18
IGBT temperature
detection failure
(tH1o)
IGBT hardware failure in temperature detection
Action and Reset
Action Condition
NTC broken or wiring failure
Action Time
When the IGBT temperature is higher than the protection level, and detection
time exceeds 100 ms, the tH1o protection activates.
Fault Treatment Parameter
N/A
Reset Method
Manual reset
Reset Condition
Immediately reset
Record
Yes
Cause
Corrective Actions
Hardware failure
Wait for 10 minutes, and then cycle the power. Check if tH1o protection still
exists. If yes, return to the factory for repair.