Chapter 14 Fault CodesMS300
573
Fault Treatment Parameter
Pr.06-73
0: No function
1: Fault and coast to stop
2: Fault and ramp to stop by the 2
nd
deceleration time
3: Warn and continue operation
When Pr.06-73 = 3, uC is a “Warning”. The warning is automatically
cleared when the output current > (Pr.06-71+0.1A).
When Pr.06-73 = 1 or 2, uC is a “Fault”. You must reset manually.
When Pr.06-71 = 1 or 2, uC is a “Fault”, and the fault is recorded.
Motor cable disconnection
Troubleshoot the connection between the motor and the load.
Improper setting of low-current
protection
Reset Pr.06-71, Pr.06-72 and Pr.06-73 to proper settings.
Check the load status.
Check if the motor capacity matches the load.