Chapter 14 Fault CodesMS300
595
Y-connection / Δ-
connection
switch error
(ydc)
An error occurs when Y-Δ switches
1. ydc occurs when the confirmation signals of Y-connection and Δ-connection
are conducted at the same time.
2. If any of confirmation signals is not conducted within Pr.05-25, ydc occurs.
Fault Treatment Parameter
Can be reset only when the confirmation signal of Y-connection is conducted if
it is Y-connection, or when the confirmation signal of Δ-connection is conducted
if it is Δ-connection.
The electromagnetic valve
operates incorrectly during Y-Δ
switch.
Check if the electromagnetic valve works normally.
If not, replace it.
Incorrect parameter setting
Check if related parameters are all set up and set correctly.
The wiring of Y-Δ switch function is
incorrect