Chapter 14 Fault CodesMS300
615
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
107
CANopen index setting
exceed limit
(CFrE)
CANopen memory error
Action and Reset
Action Condition
When you update the firmware version of the control board, the FRAM internal
data does not change, then CFrE fault occurs.
Action Time
Immediately act
Fault Treatment Parameter
N/A
Reset Method
Manual reset
Reset Condition
Pr.00-02 = 7
Record
Pr.00-21 = 3, the fault is recorded
Cause
Corrective Actions
CANopen internal memory error
1. Disable CANopen (Pr.09-36 = 0)
2. Reset CANopen (Pr.00-02 = 7)
3. Reset CANopen station address (Pr.09-36)