Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-01-3 
Frame  H 
Power (kW)  280 315 355 400 450 500 560 
Power (HP)  375 425 475 536 600 650 750 
Identity code 
47 49 51 53 55 57 59 
Rated current for 
heavy duty (A) 
550 616 683 770 866 930 1094 
Rated current for 
super heavy duty (A) 
460 550 616 683 683 866 930 
 
575V Models 
Frame  A  B 
Power (kW)  1.5 2.2 3.7 5.5 7.5 11  15 
Power (HP) 2 3 5 7.5 10 15 20 
Identity code 
505 506 507 508 509 510 511 
Rated current for 
heavy duty (A) 
2.1 3 4.6 6.9 8.3 13 16.8 
Rated current for 
normal duty (A) 
2.5 3.6 5.5 8.2 10 15.5 20 
Rated current for   
light duty (A) 
3  4.3 6.7 9.9 12.1 18.7 24.2 
 
690V Models 
Frame  C  D  E  F 
Power (kW)  18.5 22 30 37 45 55 75 90 110 132 160 200 
Power (HP)  25 30 40 50 60 75 100 125 150 175 215 270 
Identity code 
612 613 614 615 616 617 618 619 620 621 622 686 
Rated current for 
heavy duty (A) 
14 20 24 30 36 45 54 67 86 104 125 150 
Rated current for 
normal duty (A) 
20 24 30 36 45 54 67 86 104 125 150 180 
Rated current for   
light duty (A) 
24 30 36 45 54 67 86 104 125 150 180 220 
 
Frame  G  H 
Power (kW)  250 315 400 450 560 630 
Power (HP)  335 425 530 600 750 850 
Identity code 
687 626 628 629 631 632 
Rated current for 
heavy duty (A) 
180 220 290 310 420 675 
Rated current for 
normal duty (A) 
220 290 350 385 465 675 
Rated current for   
light duty (A) 
290 350 430 465 590 675 
 
 
00-02 
Parameter Reset 
 
 
   
 Default: 0 
 
 
Settings  0: No function 
1: Write protection for parameters 
5: Return kWh displays to 0 
6: Reset PLC (including CANopen Master Index) 
7: Reset CANopen Slave index 
9: Reset all parameters to defaults (base frequency is 50 Hz) 
10: Reset all parameters to defaults (base frequency is 60 Hz) 
 1: All parameters are read only except Pr.00-02, Pr.00-07 and Pr.00-08. Set Pr.00-02 to 0 before 
changing other parameter settings.