Chapter 14 Fault Codes and DescriptionsC2000  Plus 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
15 
 
Phase loss protection 
(OrP) 
Phase loss of power input 
Action and Reset 
Action condition  DC bus is lower than Pr.07-00, and DC bus ripple is higher than Pr.06-52 
Action time  N/A 
Fault treatment parameter  Pr.06-53 
Reset method  Manual reset 
Reset condition  Reset immediately when DC bus is higher than Pr.07-00 
Record  Yes 
Cause  Corrective Actions 
Phase loss of input power  Correctly install the wiring of the main circuit power. 
Single phase power input to three-
phase model 
Choose the model whose power matches the voltage. 
Power voltage changes 
If the main circuit power works normally, verify the main circuit. 
Cycle the power after checking the power, if OrP fault still occurs
factory for repair. 
Loose wiring terminal of input 
power 
Tighten the terminal screws according to the torque described in the user manual.
The input cable of three-phase 
power is cut off 
Wire correctly. 
Replace the cut off cable. 
Input power voltage changes too 
much 
Verify the setting value for Pr.06-50 Time for Input Phase 
Pr.06-52 Ripple of Input Phase Loss 
Unbalanced three-phase of input 
power 
Check the power three-phase status.