Chapter 12 Descriptions of Parameter SettingsMS300
317
02-52
Display the External Multi-function Input Terminals Used by PLC
Default: Read only
Settings
Monitor the status of PLC input terminals
Example:
When Pr.02-52 displays 0034h (hex) (that is, the value is 52 (decimal) and 0110100 (binary)), it
means that MI3, MI5 and MI6 are used by PLC.
02-53
Display the External Multi-function Output Terminals Used by PLC
Default: Read only
Settings
Monitor the status of PLC output terminals
Example:
When Pr.02-53 displays 0009h (hex) (that is, the value is 9 (decimal) and 01001 (binary)), it
means that Relay and MO1 are used by PLC.