EasyManua.ls Logo

Delta VFD25AMS23ANSAA

Delta VFD25AMS23ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Descriptions of Parameter SettingsMS300
387
start relay remains closed), and the drive executes auto-deceleration.
Situation 1: Momentary power loss, or too low and unstable power voltage, or power supply
sliding down because of sudden heavy load
Pr.07-13 = 1 and power recovers
When the power recovers and DC bus voltage exceeds the dEb return level, the drive
linearly decelerates to 0 Hz and stops. The keypad displays the “dEbwarning until you
manually reset it, so you can see the reason for the stop.
Situation 2: Momentary power loss, or too low and unstable power voltage, or power supply
sliding down because of sudden heavy load
Pr.07-13 = 2 and power recovers
During the dEb deceleration (includes 0 Hz run), if the power recovers to a voltage higher
than dEb return level, the drive maintains the frequency for three seconds and then
accelerates again. The “dEbwarning on the keypad is automatically cleared.

Table of Contents

Other manuals for Delta VFD25AMS23ANSAA

Related product manuals