Chapter 9 SpecificationsMS300
186
9-4 575V Models
575V models three-phase
Frame
A
B
C
D
Model VFD_ _ _ _ _ _ _ _AA
1A7MS53ANS
3A0MS53ANS
4A2MS53ANS
6A6MS53ANS
9A9MS53ANS
12AMS53ANS
Applicable Motor Output (kW)
0.75
1.5
2.2
3.7
5.5
7.5
Applicable Motor Output (HP)
1
2
3
5
7.5
10
Outpu
t*
Heavy Duty
Rated Output Capacity (kVA)
1.7
3
4.2
6.6
9.9
12.2
Rated Output Current (A)
1.7
3
4.2
6.6
9.9
12.2
Carrier Frequency (kHz)
2~15 (Default: 4)
Normal Duty
Rated Output Capacity (kVA)
2.1
3.6
5
8
11.5
15
Rated Output Current (A)
2.1
3.6
5
8
11.5
15
Carrier Frequency (kHz)
2~15 (Default: 4)
Input
Rated Input
Current (A)
Heavy Duty
2
3.5
4.9
7.7
11.5
14.2
Normal Duty
2.4
4.2
5.8
9.3
13.4
17.5
Rated Voltage / Frequency
Three-phase 500600 V
AC
( -1510%), 5060 Hz
Mains Input Voltage Range (V
AC
)
425660
Mains Frequency Range (Hz)
4763
Weight (kg)
0.85
0.87
1.18
1.29
2.04
Cooling Method
Convective
cooling
Fan cooling
EMC Filter
Optional
IP Rating
IP20
Table 9-9
NOTE:
1. Output*: Default is heavy duty.
2. The value of the carrier frequency is a factory default. Decrease the current value if you need to increase the
carrier frequency. Refer to Section 9-7 Derating for Ambient Temperature and Altitude for details.
3. For shock or impact load applications, select a drive with a larger capacity model.