Chapter 11 Summary of Parameter SettingsMS300
248
Pr.
Explanation
Settings
Default
09-42
CANopen Control Status
0: Not ready for use state
1: Inhibit start state
2: Ready to switch on state
3: Switched on state
4: Enable operation state
7: Quick stop active state
13: Error reaction activation state
14: Error state
Read only
09-43
CANopen Reset Index
bit 0: CANopen reset, the internal address 20XX is 0
bit 1: CANopen reset, the internal address 264X is 0
bit 2: CANopen reset, the internal address 26AX is 0
bit 3: CANopen reset, the internal address 60XX is 0
65535
09-60
Communication Card
Identification
0: No communication card
1: DeviceNet slave
2: PROFIBUS-DP slave
3: CANopen slave
5: EtherNet/IP slave
6: EtherCAT
10: Backup power supply
Read only
09-61
Firmware Version of
Communication Card
Read only
Read only
09-62
Product Code
Read only
Read only
09-63
Error Code
Read only
Read only
09-70
Communication Card
Address (For DeviceNet or
PROFIBUS)
DeviceNet: 063
PROFIBUS-DP: 1125
1
09-71
Communication Card
Speed Setting
(for DeviceNet)
Standard DeviceNet:
0: 125 Kbps
1: 250 Kbps
2: 500 Kbps
3: 1 Mbps (Delta only)
Non-standard DeviceNet (Delta only):
0: 10 Kbps
1: 20 Kbps
2: 50 Kbps
3: 100 Kbps
4: 125 Kbps
5: 250 Kbps
6: 500 Kbps
7: 800 Kbps
2

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals