Chapter 11 Summary of Parameter SettingsMS300
254
Pr.
Explanation
Settings
Default
11-27
Maximum Torque
Command
0–500%
100
11-28
Torque Offset Source
0: Disable
1: Analog signal input
2: RS-485 communication (Pr.11-29)
3: Controlled through external terminals
(Pr.11-3011-32)
0
11-29
Torque Offset Setting
-100.0–100.0%
0.0
11-30
High Torque Offset
-100.0–100.0%
30.0
11-31
Middle Torque Offset
-100.0–100.0%
20.0
11-32
Low Torque Offset
-100.0–100.0%
10.0
11-33
Torque Command Source
0: Digital keypad
1: RS-485 communication (Pr.11-34)
2: Analog signal input (Pr.03-00)
3: CANopen
5: Communication Card
0
11-34
Torque Command
-100.0–100.0%
0.0
11-35
Torque Command Filter
Time
0.000–1.000 sec.
0.000
11-36
Speed Limit Selection
0: Set by Pr.11-37 (forward speed limit) and Pr.11-38
(reverse speed limit)
1: Set by Pr.00-20 (Master frequency command (AUTO,
REMOTE) source) and Pr.11-37, Pr.11-38
2: Set by Pr.00-20 (master frequency command (AUTO,
REMOTE) source)
0
11-37
Forward Speed Limit
(Torque Mode)
0–120%
10
11-38
Reverse Speed Limit
(Torque Mode)
0–120%
10
11-41
PWM Mode Selection
0: Two-phase modulation mode
2: Space vector modulation mode
2
11-42
System Control Flag
0000–FFFFh
0000