EasyManuals Logo

Delta VFD2A8MS21ANSAA User Manual

Delta VFD2A8MS21ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #294 background imageLoading...
Page #294 background image
Chapter 12 Descriptions of Parameter SettingsMS300
285
Common settings for the V/F curve:
(1) General purpose
(2) For fan and hydraulic machinery
(3) High starting torque
01-09
Start-up Frequency
Default: 0.50
Settings
0.00–599.00 Hz
When the starting frequency (Pr.01-09) is larger than the Minimum Output Frequency of Motor 1
(Pr.01-07), the drive’s frequency output starts when the starting frequency (Pr.01-09) reaches
the F command. Refer to the following diagram for details.
Fcmd = frequency command;
Fstart = start-up frequency (Pr.01-09);
fstart = actual start-up frequency of the drive;
Fmin = 4th output frequency setting (Pr.01-07 / Pr.01-41);
Flow = output frequency lower limit (Pr.01-11)

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals