Chapter 12 Descriptions of Parameter SettingsMS300
351
MSI Motor Spec.
(Rated Speed 1500 rpm)
Drive Parameter /
Default
MSI Motor Spec.
(Rated Speed 3000 rpm)
Drive Parameter /
Default
Model
Power
(kW)
Pr.05-51
Motor Code
(User set)
Model
Power
(kW)
Pr.05-51
Motor Code
(User set)
MSI75B-15CDXS21A
0.75
1004
MSI75B-30CDXS21A
0.75
1204
MSI11C-15CDXS21A
1.1
1005
MSI11C-30CDXS21A
1.1
1205
MSI15C-15CDXS21A
1.5
1006
MSI15C-30CDXS21A
1.5
1206
MSI22C-15CDXS21A
2.2
1007
MSI22C-30CDXS21A
2.2
1207
MSI30C-15CDXS21A
3
1008
MSI30C-30CDXS21A
3
1208
MSI40C-15CDXS21A
4
1010
MSI40C-30CDXS21A
4
1210
MSI55C-15CDXS21A
5.5
1011
MSI55C-30CDXS21A
5.5
1211
MSI75C-15CDXS21A
7.5
1012
MSI75C-30CDXS21A
7.5
1212
MSI11D-15CDXS21A
11
1013
MSI11D-30CDXS21A
11
1213
MSI15D-15CDXS21A
15
1014
MSI15D-30CDXS21A
15
1214
MSI18D-15CDXS21A
18.5
1015
MSI18D-30CDXS21A
18.5
1215
MSI22D-15CDXS21A
22
1016
MSI22D-30CDXS21A
22
1216
05-64
Full-load Current for Induction Motor 3 (A)
Default: Depending on the
model power
Settings
10120% of the drive’s rated current
Set this value according to the rated current of the motor as indicated on the motor nameplate.
The default is 90% of the drive’s rated current.
Example: The rated current for a 7.5 HP (5.5 kW) motor is 25 A. The default is 22.5 A.
The setting range is 2.530 A (25 × 10% = 2.5 A and 25 × 120% = 30 A).
05-65
Rated Power for Induction Motor 3 (kW)
Default: Depending on the
model power
Settings
0.00–655.35 kW
Sets the rated power for motor 3. The default is the drive’s power value.
05-66
Rated Speed for Induction Motor 3 (rpm)
Default: Depending on the
motor’s number of poles
Settings
0–xxxxx rpm (Depending on the motor’s number of poles)
1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
Sets the rated speed for the motor as indicated on the motor nameplate.
05-67
Number of Poles for Induction Motor 3
Default: 4
Settings
2–20
Sets the number of poles for the motor (must be an even number).

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals