EasyManua.ls Logo

Delta VFD2A8MS21ANSAA

Delta VFD2A8MS21ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Descriptions of Parameter SettingsMS300
380
06-80
Fire Mode
Default: 0
Settings
0: Disable
1: Forward (counterclockwise) operation
2: Reverse (clockwise) operation
Use this parameter with multi-function input terminal setting 58 or 59, and multi-function output
terminal setting 53.
0: Fire detection is invalid.
1: The motor operates in a counterclockwise direction (U, V, W).
2: The motor operates in a clockwise direction (U, W, V).
06-81
Operating Frequency in Fire Mode
Default: 60.00
Settings
0.00–599.00 Hz
Enables fire mode (Pr.06-70 = 1 or 2) and sets the operation frequency in fire mode (Pr.06-81).
The drive operates with operation frequency in fire mode when the fire mode is enabled.
06-88
Operation Times in Fire Mode
Default: Read only
Settings
0–65535 times
Counts once when fire mode operates for 4 minutes.

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Related product manuals