EasyManuals Logo

Delta VFD2A8MS21ANSAA User Manual

Delta VFD2A8MS21ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #422 background imageLoading...
Page #422 background image
Chapter 12 Descriptions of Parameter SettingsMS300
413
Switch according to the deviation:
When the deviation absolute value between the set point and feedback is smaller than
Pr.08-76 (PID2 Parameter Switch Deviation 1), the first group PID parameters are used.
When the deviation absolute value between the set point and feedback is larger than Pr.08-
77 (PID2 Parameter Switch Deviation 2), the second group PID parameters are used.
When the deviation absolute value between the set point and feedback is between Pr.08-76
and Pr.08-77, the PID parameter is the linear interpolation value between the two PID
parameter groups.
08-78
Allowed Reverse Running Time after Start-Up
Default: 0.0
Settings
0.06553.5 sec.
When Pr.08-78 is not set to 0, the allowed reverse running time after start-up is enabled.
When it is set to 1 second, the PID control is not allowed to change the running direction within
0–1 seconds of starting time (Pr.08-21 = 0), and is allowed to change after 1 second of starting
time (Pr.08-21 = 1).

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals