Chapter 12 Descriptions of Parameter SettingsMS300
420
09-71
Communication Card Speed Setting (for DeviceNet)
Default: 2
Settings
Standard DeviceNet:
0: 125 Kbps
1: 250 Kbps
2: 500 Kbps
3: 1 Mbps (Delta Only)
Non-standard DeviceNet: (Delta only):
0: 10 Kbps
1: 20 Kbps
2: 50 Kbps
3: 100 Kbps
4: 125 Kbps
5: 250 Kbps
6: 500 Kbps
7: 800 Kbps
8: 1 Mbps
09-72
Additional Settings for Communication Card Speed (for DeviceNet)
Default: 0
Settings
0: Disable
In this mode, the baud rate can only be 125 Kbps, 250 Kbps, 500 Kbps, or
1 Mbps in standard DeviceNet speed.
1: Enable
In this mode, the DeviceNet baud rate can be same as that for CANopen
(08).
Use this parameter with Pr.09-71.
0: The baud rate can only be set to 125 Kbps, 250 Kbps and 500 Kbps (baud rate 0, 1, 2 and 3)
as a standard DeviceNet speed.
1: The DeviceNet communication rate can be the same as that for CANopen (setting 0–8).
09-75
Communication Card IP Configuration (for EtherNet)
Default: 0
Settings
0: Static IP
1: Dynamic IP (DHCP)
0: Set the IP address manually.
1: IP address is dynamically set by the host controller.