EasyManuals Logo

Delta VFD2A8MS21ANSAA User Manual

Delta VFD2A8MS21ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #438 background imageLoading...
Page #438 background image
Chapter 12 Descriptions of Parameter SettingsMS300
429
electromagnetic noise might be louder if the setting value is too high.
The system uses this parameter when the motor’s parameter is “Auto”. This parameter
influences the angle estimation accuracy.
When the ratio of the salient pole (Lq / Ld) is lower, increase Pr.10-52 to make the angle
detection accurate.
Pr.10-52 is valid only when Pr.10-53 = 2.
10-53
Angle Detection Method
Default: 0
Settings
0: Disabled
1: Force attracting the rotor to zero degrees
2: High frequency injection
3: Pulse injection
Set to 2 for IPM; set to 3 for SPM. If these settings cause problems, then set the parameter to 1.

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals