Chapter 13 Warning CodesMS300
473
Digital Keypad KPMS-LE01
ID No.
Display on LCD Keypad
Warning Name
Description
1
Communication error 1
(CE1)
RS-485 Modbus illegal function code
Action and Reset
Action Condition
When the function code is not 03, 06, 10 and 63
Action Time
Immediately act
Warning Setting Parameter
N/A
Reset Method
“Warningoccurs when Pr.09-02 = 0 and the motor drive keeps running. The
drive resets automatically when receiving the correct function code.
Reset Condition
Immediately reset
Record
N/A
Cause
Corrective Actions
Incorrect communication
command from upper unit
Check if the communication command is correct.
Malfunction caused by
interference
Verify the wiring and grounding of the communication circuit. It is recommended
to separate the communication circuit from the main circuit, or wire in 90 degree
for effective anti-interference performance.
Different communication setting
from the upper unit
Check if the setting for Pr.09-04 is the same as the setting for the upper unit.
Disconnection or bad connection
of the cable
Check the cable and replace it if necessary.

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals