EasyManuals Logo

Delta VFD2A8MS21ANSAA User Manual

Delta VFD2A8MS21ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #565 background imageLoading...
Page #565 background image
Chapter 14 Fault CodesMS300
556
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
9
Over-voltage during
constant speed
(ovn)
DC bus over-voltage at constant speed.
When ovn occurs, the drive closes the gate of the
output immediately, the motor runs freely, and the
display shows an ovn error.
Action and Reset
Action Condition
230V models: 410 V
DC
460V models: 820 V
DC
575V models: 1116 V
DC
Action Time
Immediately act when the DC bus voltage is higher than the level
Fault Treatment Parameter
N/A
Reset Method
Manual reset
Reset Condition
Reset only when the DC bus voltage is lower than 90% of the over-voltage level
Record
Yes
Cause
Corrective Actions
Impulsive change of the load
1. Connect the brake resistor, braking unit or DC bus to the drive.
2. Reduce the load.
3. Replace the drive with a larger capacity model.
4. Adjust the braking level (Pr.07-01 or bolt position of the brake unit).
The setting for stall prevention
level is smaller than no-load
current
The setting of the stall prevention level should be larger than no-load current
Regenerative voltage of motor
inertia
Use over-voltage stall prevention function (Pr.06-01)
Use a braking unit or DC bus
Power voltage is too high
Check if the input voltage is within the rated AC motor drive input voltage range,
and check for possible voltage spikes.
ON/OFF switch action of phase-in
capacitor in the same power
system
If the phase-in capacitor or active power supply unit acts in the same power
system, the input voltage may surge abnormally in a short time. In this case,
install an AC reactor.
Motor ground fault
The ground short circuit current charges the capacitor in the main circuit
through the power. Check if there is ground fault on the motor cable, wiring box
and its internal terminals.
Troubleshoot the ground fault.
Incorrect wiring of brake resistor or
brake unit
Check the wiring of the brake resistor or braking unit.
Malfunction caused by
interference
Verify the wiring of the control circuit and the wiring/grounding of the main
circuit to prevent interference.

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals