Chapter 14 Fault CodesMS300
558
Low-voltage during
acceleration
(LvA)
DC bus voltage is lower than Pr.06-00 setting value
during acceleration
Pr.06-00 (Default = depending on the model)
Immediately act when the DC bus voltage is lower than Pr.06-00
Fault Treatment Parameter
Reset when the DC bus voltage is higher than Pr.06-00 + 30 V
Improve power supply condition.
Adjust voltage to the power range of the drive
Start up the motor with large
capacity
Check the power system.
Increase the capacity of power equipment.
Reduce the load.
Increase the drive capacity.
Increase the acceleration time.
Check if there is short circuit plate
or any DC reactor installed
between terminal +1 and +2
Connect short circuit plate or DC reactor between terminal +1 and +2.
If the error still exists, return to the factory for repair.