Chapter 14 Fault CodesMS300
626
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
141
GFF occurs before run
(b4GFF)
The ground short circuit detected when the output
wiring detection is performed before the drive runs.
Action and Reset
Action Condition
250% of the rated current
Action Time
Immediately act
Fault Treatment Parameter
N/A
Reset Method
Manual reset
Reset Condition
Reset in five seconds after the fault is cleared
Record
Yes
Cause
Corrective Actions
Incorrect wiring for the motor
Check if the motor’s internal wiring and the UVW wiring of the drive output
terminal are correct.
Short-circuit at motor output due to
poor insulation wiring
Check the motor cable and remove causes of the short circuits, or replace the
cable before turning on the power.
Check for possible burnout or
aging insulation of the motor
Check the motor insulation value with megger. Replace the motor if the
insulation is poor.