EasyManuals Logo

Delta VFD2A8MS21ANSAA User Manual

Delta VFD2A8MS21ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #638 background imageLoading...
Page #638 background image
Chapter 14 Fault CodesMS300
629
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
144
Auto-tune error 3
(AuE3)
No load current I
0
measurement error when the motor
parameter automatically detects.
Action and Reset
Action Condition
Software detection
Action Time
Immediately act
Fault Treatment Parameter
N/A
Reset Method
Manual reset
Reset Condition
Immediately reset
Record
Yes
Cause
Corrective Actions
Incorrect settings for the motor
parameter (rated current)
Check the settings for Pr.05-01 / Pr.05-13 / Pr.05-34.
Motor error
Check if the motor works normally.

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals