Chapter 16 PLC Function ApplicationsMS300
761
Pr.09-33 are defined on the basis of whether reference commands have been
cleared before the PLC operation
bit 0: Prior to PLC scanning procedures, acts on whether the target frequency has
been cleared to 0. This is written to the FREQ command when the PLC is
ON.
bit 1: Prior to PLC scanning procedures, acts on whether the target torque has
been cleared to 0. This is written to the TORQ command when the PLC is
ON.
bit 2: Prior to PLC scanning procedures, acts on whether speed limits in the
torque mode have been cleared to 0. This is written to the TORQ command
when the PLC is ON.
Example: When using r to write a program,
END
K2000
M0
K1000
K1000
FREQ
If we force M0 to 1, the frequency command is 20.00 Hz; but when M0 is
set to 0, there is a different situation.
Case 1: When the Pr.09-33 bit 0 is 0, and M0 is set as 0, then the frequency
command remains at 20.00 Hz.
Case 2: When the Pr.09-33 bit 0 is 1, and M0 is set as 0, then the frequency
command changes to 0.00 Hz
This is because when the Pr.09-33 bit 0 is 1 prior to PLC scanning procedures, the
frequency first reverts to 0.
When the Pr.09-33 bit 0 is 0, the frequency does not revert to 0.

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals