Appendix A. Modbus ProtocolMS300
784
RTU mode:
START
Defined by a silent interval of larger than / equal to 3.5 char
Address
Communication address: 8-bit binary address
Function
Command code: 8-bit binary command
DATA (n-1)
Contents of data:
N × 8-bit data, n ≤ 16
…….
DATA 0
CRC Check Low
CRC checksum:
one 16-bit CRC checksum consists of 2 8-bit binary
characters
CRC Check High
END
Defined by a silent interval of larger than / equal to 3.5 char
2. Communication address (Address)
00H: broadcast to all AC motor drives
01H: AC motor drive of address 01
0FH: AC motor drive of address 15
10H: AC motor drive of address 16
:
FEH: AC motor drive of address 254
3. Function (function code) and data (data characters)
03H: read data from a register
Example: Reading two continuous data from register address 2102H, AMD address is 01H.
ASCII mode:
Command Message
Response Message
STX
‘:’
STX
‘:’
Address
‘0’
Address
‘0’
‘1’
‘1’
Function
‘0’
Function
‘0’
‘3’
‘3’
Starting register
‘2’
Number of register
(count by byte)
‘0’
‘1’
‘4’
‘0’
Content of starting
register 2102H
‘1’
‘2’
‘7’
Number of register
(count by word)
‘0’
‘7’
‘0’
‘0’
‘0’
Content of register 2103H
‘0’
‘2’
‘0’
LRC Check
‘D’
‘0’
‘7’
‘0’
END
CR
LRC Check
‘7’
LF
‘1’
END
CR
LF

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals