EasyManuals Logo

Delta VFD450C43S-21 User Manual

Delta VFD450C43S-21
1259 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #1017 background imageLoading...
Page #1017 background image
Chapter 14 Fault Codes and DescriptionsC2000 Plus
14-114
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
188
Load estimation error
(TLAT)
The initial load estimation error occurs when using
Explorer for ASR Auto Tune.
Action and Reset
Action condition
The estimated load variation cannot converge to 10% and below.
Action time
60 seconds
Fault treatment parameter
N/A
Reset method
Manual reset
Reset condition
Reset immediately
Record
Yes
Cause
Corrective Actions
The initial load estimation cannot
converge
Verify if the load is stable. It cannot estimate the inertia correctly if the load
vibrates.
Initial load is too large
Increase torque command to support the load.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD450C43S-21 and is the answer not in the manual?

Delta VFD450C43S-21 Specifications

General IconGeneral
BrandDelta
ModelVFD450C43S-21
CategoryDC Drives
LanguageEnglish

Related product manuals