Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-06-8 
 
06-07 
Over-Torque Detection Level (OT1) 
 
 
   
 Default: 120 
 
 
Settings 10–250%  
(100% corresponds to the rated current of the drive) 
 
06-08 
Over-Torque Detection Time (OT1) 
 
 
   
 Default: 0.1 
 
 
Settings 0.0–60.0 sec. 
 
06-10 
Over-Torque Detection Level (OT2) 
 
 
   
 Default: 120 
 
 
Settings 10–250%  
(100% corresponds to the rated current of the drive) 
 
06-11 
Over-Torque Detection Time (OT2) 
 
 
   
 Default: 0.1 
 
 
Settings 0.0–60.0 sec. 
 When the output current exceeds the over-torque detection level (Pr.06-07 or Pr.06-10) and 
exceeds the over-torque detection time (Pr.06-08 or Pr.06-11), the over-torque detection follows 
the setting of Pr.06-06 and Pr.06-09. 
 When you set Pr.06-06 or Pr.06-09 to 1 or 3, an ot1 / ot2 warning displays while the drive keeps 
running after over-torque detection. The warning remains on until the output current is smaller 
than 5% of the over-torque detection level.
 
 
 When you set Pr.06-06 or Pr.06-09 to 2 or 4, an ot1 / ot2 warning displays and the drive stops 
running after over-torque detection. The drive does not run until you manually reset it.