Chapter 12 Description of Parameter SettingsCP2000   
 
12.1-02-9 
time for confirmation. The confirmation prevents interference that could cause error in the input to 
the digital terminals. In the meanwhile, it delays the response time, though confirmation improves 
accuracy. 
 
 
Multi-function Input Mode Selection 
 
 
  Default: 0000h   
  Settings 0000h–FFFFh (0: N.O.; 1: N.C.) 
 The parameter setting is in hexadecimal.   
 This parameter sets the status of the multi-function input signal (0: normal open;1: normal close) 
and it is not affected by the status of SINK / SOURCE. 
 bit2–bit15 correspond to MI1–MI14. 
 The default for bit0 is FWD terminal, and the default for bit1 is REV terminal. You cannot use this 
parameter to change the input mode. 
 You can change the terminal ON / OFF status through communications. 
For example, MI1 is set to 1 (multi-step speed command 1), MI2 is set to 2 (multi-step speed 
command 2). Then the forward + 2
nd
 step speed command=1001
2
 =9
10
. As long as Pr.02-12=9 is 
set through communications, there is no need to wire any multi-function terminal to run forward 
with the second step speed. 
bit15  bit14  bit13  bit12  bit11  bit10  bit9  bit8  bit7  bit6  bit5  bit4  bit3  bit2  bit1  bit0 
MI15  MI14  MI13  MI12  MI11  MI10  MI8  MI7  MI6  MI5  MI4  MI3  MI2  MI1  REV  FWD 
 
  Multi-function Output 1 (Relay1) 
     Default: 11 
 
 
Multi-function Output 2 (Relay2) 
     Default: 1 
 
 
Multi-function Output 3 (Relay3) 
     Default: 66 
 
 
Output Terminal of I/O Extension Card (MO10) or (RA10) 
 
 
Output Terminal of I/O Extension Card (MO11) or (RA11) 
 
 
Output Terminal of I/O Extension Card (RA12) 
 
 
Output Terminal of I/O Extension Card (RA13) 
 
 
Output Terminal of I/O Extension Card (RA14) 
 
 
Output Terminal of I/O Extension Card (RA15) 
 
 
Output Terminal of I/O Extension Card (MO16 Virtual Terminal)   
 
 
Output Terminal of I/O Extension Card (MO17 Virtual Terminal) 
 
 
Output Terminal of I/O Extension Card (MO18 Virtual Terminal) 
 
 
Output Terminal of I/O Extension Card (MO19 Virtual Terminal)   
 
 
Output Terminal of I/O Extension Card (MO20 Virtual Terminal)   
     Default: 0 
   Settings 
 
 
  
   0: No function 
 
 
  
   1: Indication during RUN