Chapter 14 Fault Codes and DescriptionsCP2000 
 
14-9 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
10 
 
Over-voltage at stop 
(ovS) 
Over-voltage at stop 
Action and Reset 
Action level 
230V series: 410 V
DC
 
460V series: 820 V
DC 
575V series: 1116 V
DC 
690V series: 1318 V
DC
 
Action time  Immediately act when DC bus voltage is higher than the level 
Fault treatment parameter  N/A 
Reset method  Manual reset 
Reset condition  Reset only when DC bus voltage is lower than 90% of over-voltage level 
Record  Yes 
Cause  Corrective Actions 
Power voltage is too high 
Check if the input voltage is within the rated AC motor drive input voltage range, 
and check for possible voltage spikes. 
ON/OFF switch action of phase-in 
capacitor in the same power 
system 
If the phase-in capacitor or active power supply unit activates in the same power 
system, the input voltage may surge abnormally in a short time. In this case, 
install an AC reactor. 
Incorrect wiring of brake resistor or 
brake unit 
Check the wiring of brake resistor or brake unit. 
Malfunction caused by interference 
Verify the wiring of the control circuit and wiring/grounding of the main circuit to 
prevent interference. 
Hardware failure in voltage 
detection 
Check if other error code such as cd1–cd3 occur after cycling the power. If yes, 
return to the factory for repair. 
Motor ground fault 
The ground short circuit current charges the capacitor in the main circuit through 
the power. Check if there is ground fault on the motor cable, wiring box and its 
internal terminals. 
Troubleshoot the ground fault. 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
11 
 
Low-voltage during 
acceleration   
(LvA) 
DC  bus  voltage  is  lower  than  Pr.06-00  setting  value 
during acceleration 
Action and Reset 
Action level  Pr.06-00 (Default = depending on the model) 
Action time  Immediately act when DC bus voltage is lower than Pr.06-00 
Fault treatment parameter  N/A 
Reset method  Manual reset 
Reset condition 
Reset when DC bus voltage is higher than Pr.06-00 + 30V (Frame A–D) / 40V 
(Frame E and below) 
Record  Yes 
Cause  Corrective Actions 
Power-off  Improve power supply condition. 
Power voltage changes  Adjust voltage to the power range of the drive 
Start up the motor with large 
capacity 
Check the power system. 
Increase the capacity of power equipment. 
The load is too large 
Reduce the load. 
Increase the drive capacity. 
Increase the acceleration time. 
DC bus  Install DC reactor(s). 
Check if there is short-circuit plate 
or any DC reactor installed 
between terminal +1 and +2 
Connect short circuit plate or DC reactor between terminal +1 and +2. 
If the error still exists, return to the factory for repair.