Chapter 14 Fault Codes and DescriptionsCP2000 
 
14-10
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
12 
 
Low-voltage during 
deceleration   
(Lvd) 
DC  bus  voltage  is  lower  than  Pr.06-00  setting  value 
during deceleration 
Action and Reset 
Action level  Pr.06-00 (Default = depending on the model) 
Action time  Immediately act when DC bus voltage is lower than Pr.06-00 
Fault treatment parameter  NA 
Reset method  Manual reset 
Reset condition 
Reset when DC bus voltage is higher than Pr.06-00 + 30V (Frame A
–D) / 40V 
(Frame E and above) 
Record  Yes 
Cause  Corrective Actions 
Power-off  Improve power supply condition. 
Power voltage changes  Adjust voltage to the power range of the drive. 
Start up the motor with large 
capacity 
Check the power system. 
Increase the capacity of power equipment. 
Sudden load 
Reduce the load. 
Increase the drive capacity. 
DC bus  Install DC reactor(s). 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
13 
 
Low-voltage at 
constant speed   
(Lvn) 
DC bus voltage is lower than Pr.06-00 setting value at 
constant speed 
Action and Reset 
Action level  Pr.06-00 (Default = depending on the model) 
Action time  Immediately act when DC bus voltage is lower than Pr.06-00 
Fault treatment parameter  NA 
Reset method  Manual reset 
Reset condition 
Reset when DC bus voltage is higher than Pr.06-00 + 30V (Frame A
–D) / 40V 
(Frame E and above) 
Record  Yes 
Cause  Corrective Actions 
Power-off  Improve power supply condition. 
Power voltage changes  Adjust voltage to the power range of the drive 
Start up the motor with large 
capacity 
Check the power system. 
Increase the capacity of power equipment. 
Sudden load 
Reduce the load. 
Increase the drive capacity. 
DC bus  Install DC reactor(s).