Chapter 11 Summary of Parameter SettingsME300
11-5
Pr. Explanation Settings Default
01Axh: inWG
01Bxh: ftWG
01Cxh: Psi
01Dxh: Atm
01Exh: L/s
01Fxh: L/m
020xh: L/h
021xh: m3/s
022xh: m3/h
023xh: GPM
024xh: CFM
00-26
Maximum user-defined
value
0: Disable
0–65535 (when Pr.00-25 set to no decimal place)
0.0–6553.5 (when Pr.00-25 set to 1 decimal place)
0.00–655.35 (when Pr.00-25 set to 2 decimal places)
0.000–65.535 (when Pr.00-25 set to 3 decimal places)
0
00-27 User-defined value Read only Read only
00-29 LOCAL / REMOTE mode
0: Standard HOA function
1: When switching between local and remote, the drive
stops.
2: When switching between local and remote, the drive
runs with REMOTE settings for frequency and
operation status.
3: When switching between local and remote, the drive
runs with LOCAL settings for frequency and operation
status.
4: When switching between local and remote, the drive
runs with LOCAL settings when switched to Local and
runs with REMOTE settings when switched to Remote
for frequency and operation status.
0
00-30
Master frequency
command (HAND) source
0: Digital keypad
1: RS-485 communication
2: External analog input (refer to Pr.03-00)
3: External UP/DOWN terminal
7: Digital keypad dial
0
00-31
Operation command
(HAND) source
0: Digital keypad
1: External terminals
2: RS-485 communication
0
00-32
Digital keypad STOP
function
0: Disable STOP key
1: Enable STOP key
0