Chapter 11 Summary of Parameter SettingsME300
11-20
Pr. Explanation Settings Default
05-21
Stator inductance (Lx)
for induction motor 2
0.0–6553.5 mH
#.#
05-22
Multi-motors (induction)
selection
1: Motor 1
2: Motor 2
1
05-23
Frequency for
Y-connection /Δ-connection
switch for an induction
motor
0.00–599.00 Hz
60.00
05-24
Y-connection /Δ-connection
switch for an induction
motor
0: Disable
1: Enable
0
05-25
Delay time for
Y-connection /Δ-connection
switch for an induction
motor
0.000–60.000 sec.
0.200
05-28
Accumulated Watt-hour
for a motor (W-hour)
Read only 0.0
05-29
Accumulated Watt-hour
for a motor in low word
(kW-hour)
Read only 0.0
05-30
Accumulated Watt-hour
for a motor in high word
(MW-hour)
Read only 0.0
05-31
Accumulated motor
operation time (minutes)
0–1439 min. 0
05-32
Accumulated motor
operation time (days)
0–65535 days 0
05-33
Induction motor (IM) or
permanent magnet
synchronous motor
selection
0: Induction motor
1: SPM
2: IPM
0
05-34
Full-load current for a
permanent magnet
synchronous motor
0–120% of the drive’s rated current #.#
05-35
Rated power for a
permanent magnet
synchronous motor
0.00–655.35 kW #.##
05-36
Rated speed for a
permanent magnet
synchronous motor
0–65535 rpm 2000