Chapter 12 Description of Parameter SettingsME300
12.1-02-13
Settings Functions Descriptions
26 Reverse command Active when the operation direction is reverse.
29
Output when frequency
≥ Pr.02-34
Active when the frequency is ≥ Pr.02-34
(actual output H ≥ Pr.02-34).
30
Output when frequency
< Pr.02-34
Active when frequency is < Pr.02-34
(actual output H < Pr.02-34).
31
Y-connection for the
motor coil
Active when Pr.05-24 = 1, the frequency output is lower than
Pr.05-23 minus 2 Hz, and the time is longer than Pr.05-25.
32
∆-connection for the
motor coil
Active when Pr.05-24 = 1, the frequency output is higher than
Pr.05-23 plus 2 Hz, and the time is longer than Pr.05-25.
33
Zero speed
(actual output
frequency)
Active when the actual output frequency is 0
(the drive is in RUN mode).
34
Zero speed includes
stop (actual output
frequency)
Active when the actual output frequency is 0 or stopped.
35
Error output selection 1
(Pr.06-23)
Active when Pr.06-23 is ON.
36
Error output selection 2
(Pr.06-24)
Active when Pr.06-24 is ON.
37
Error output Selection 3
(Pr.06-25)
Active when Pr.06-25 is ON.
38
Error output Selection 4
(Pr.06-26)
Active when Pr.06-26 is ON.
40
Speed reached
(including Stop)
Active when the output frequency reaches the setting frequency
or stopped.
42 Crane function
Use this function with Pr.02-34 and Pr.02-58.
Refer to Pr.02-34 and Pr.02-58 for details.
43
Motor speed output
< Pr.02-47
Active when motor speed is less than Pr.02-47.
44 Low current output Use this function with Pr.06-71–Pr.06-73.