EasyManuals Logo

Delta VFD4A2ME43ANNAA User Manual

Delta VFD4A2ME43ANNAA
403 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #390 background imageLoading...
Page #390 background image
Chapter 14 Fault Codes and DescriptionsME300
14-27
Fault treatment parameter N/A
Reset method Manual reset
Reset condition Immediately reset
Record Yes
Cause Corrective Actions
Incorrect motor wiring Wire the motor correctly.
Motor error Check if the motor works normally.
The electromagnetic contactor is
used as an open state on the
output side of the drive (U/V/W).
Verify that the three-phases of the electromagnetic valve are all closed.
Motor U/V/W wire error Check if the wires are broken.
ID No. Display on LCM Keypad Fault Name Fault Descriptions
144
Auto-tune error 3
(AUE3)
No load current I
0
measurement error when motor
parameter automatically detects.
Action and Reset
Action level Software detection
Action time Immediately act
Fault treatment parameter N/A
Reset method Manual reset
Reset condition Immediately reset
Record Yes
Cause Corrective Actions
Incorrect settings for the motor
parameter (rated current)
Check the settings for Pr.05-01 / Pr.05-13 / Pr.05-34.
Motor error Check if the motor works normally.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD4A2ME43ANNAA and is the answer not in the manual?

Delta VFD4A2ME43ANNAA Specifications

General IconGeneral
BrandDelta
ModelVFD4A2ME43ANNAA
CategoryDC Drives
LanguageEnglish

Related product manuals