Chapter 12 Description of Parameter SettingsCP2000   
 
12.1-02-13 
Settings  Functions  Descriptions 
37 
Error output selection 3 
(Pr.06-25) 
Active when Pr.06-25 is ON. 
38 
Error output selection 4 
(Pr.06-26) 
Active when Pr.06-26 is ON. 
40 
Speed reached 
(including STOP) 
Active  when  the  output  frequency reaches  the  setting  frequency  or 
stopped. 
44  Low current output  This function needs to be used with Pr.06-71–Pr.06-73 
45 
UVW output 
electromagnetic valve 
switch   
Use this function with external terminal input = 49 (drive enabled) and 
external  terminal  output  =  45  (electromagnetic  valve  enabled),  and 
then the electromagnetic valve is ON or OFF according to the status of 
the drive.   
 
46  Master dEb output 
When dEb rises at master, MO sends a dEb signal to the slave. 
Output the message when the master triggers dEb. This ensures that 
the slave also triggers dEb. Then slave follows the deceleration time 
of the master to stop simultaneously with the master. 
50 
Output control for 
CANopen 
Control multi-function output terminals through CANopen. 
To control RY2, set Pr.02-14 = 50. 
The mapping table of the CANopen DO is shown in the following table: 
Physical 
terminal 
Setting of related 
parameters 
Attribute  Corresponding Index 
RY1  Pr.02-13 = 50  RW  The bit0 at 2026-41 
RY2  Pr.02-14 = 50  RW  The bit1 at 2026-41 
RY3  Pr.02-15 = 50  RW  The bit2 at 2026-41 
MO10/RY10  Pr.02-36 = 50  RW  The bit5 at 2026-41 
MO11/RY11  Pr.02-37 = 50  RW  The bit6 at 2026-41 
RY12  Pr.02-38 = 50  RW  The bit7 at 2026-41 
RY13  Pr.02-39 = 50  RW  The bit8 at 2026-41 
RY14  Pr.02-40 = 50  RW  The bit9 at 2026-41 
RY15  Pr.02-41 = 50  RW  The bit10 at 2026-41 
Refer to Section 15-3-5 for more information.