Chapter 12 Description of Parameter SettingsCP2000 
 
12.1-06-23 
 
 When Pr.06-58=0.00 Hz, PT100 function is disabled. 
Example: 
When using PT100, if the motor temperature is higher than 135°C (275°F), the drive starts to 
count the delay time for auto-deceleration (Pr.06-59). The drive decreases the motor frequency to 
the setting for Pr.06-58 when it reaches the delay time  count value. The drive operates at the 
frequency set for Pr.06-58 until the motor temperature is lower than 135°C (275°F). If the motor 
temperature  is  higher  than  150°C  (302°F),  the  drive  automatically  decelerates  to  STOP  and 
displays the warning “oH3”.   
Set up process:   
1.  Switch AFM2 to 0
–20 mA on the I/O control terminal block. (Refer to Figure 1, PT100 wiring 
diagram) 
2.  Wiring (Refer to Figure 1, PT100 wiring diagram): 
Connect external terminal AFM2 to (+) 
Connect external terminal ACM to (-)   
Connect external terminals AFM2 and AVI1 to “short-circuit” 
3.  Set Pr.03-00=11 or Pr.03-23=23 or Pr.03-33=45% (9 mA). 
4.  Refer to the RTD temperature and resistance comparison table 
Temperature=135°C, resistance=151.71 ; input current: 9 mA, voltage: about 1.37 V
DC
 
Temperature=150°C, resistance=157.33 ; input current: 9 mA, voltage: about 1.42 V
DC
 
5.  When  the RTD  temperature is  >  135°C,  the  drive  decelerates  to  the specified  operation 
frequency  automatically.  Then,  Pr.06-56=1.37  and  Pr.06-58=10  Hz.  When  Pr.06-58=0,  it 
disables the specified operation frequency. 
6.  When the RTD temperature is > 150°C, the drive outputs a fault, decelerates to STOP, and 
displays the warning ‘oH3’. Then, Pr.06-57=1.42 and Pr.06-29=1 (warn and ramp to stop). 
 
 
Software Detection GFF Current Level 
  
 
  Default: 60.0 
  Settings  0.0–6553.5% (100% corresponds to the light-load rated current of the drive) 
 
 
Software Detection GFF Filter Time 
  
 
  Default: 0.10 
  Settings  0.00–655.35 sec. 
  When the drive detects that the unbalanced three-phase output current is higher than the setting 
for Pr.06-60, GFF protection activates. The drive then stops output. 
 
 
Operation Time of Fault Record 1 (Day) 
 
 
Operation Time of Fault Record 2 (Day) 
 
 
Operation Time of Fault Record 3 (Day) 
 
 
Operation Time of Fault Record 4 (Day) 
  
 
  Default: Read only 
  Settings  0–65535 days