Chapter 12 Description of Parameter SettingsCP2000 
 
 
12.1-09-6 
ASCII Mode 
Command Message:    Response Message 
STX  ‘:’    STX  ‘:’ 
ADR 1 
ADR 0 
‘0’   
ADR 1 
ADR 0 
‘0’ 
‘1’    ‘1’ 
CMD 1  ‘1’    CMD 1  ‘1’ 
CMD 0  ‘0’    CMD 0  ‘0’ 
Target register 
‘0’   
Target register 
‘0’ 
‘4’    ‘4’ 
‘0’    ‘0’ 
‘0’    ‘0’ 
Number of register 
(count by word) 
‘0’   
Number of register 
(count by word) 
‘0’ 
‘0’    ‘0’ 
‘0’    ‘0’ 
‘2’    ‘2’ 
Number of register 
(count by byte) 
‘0’   
LRC Check 
‘E’ 
‘4’    ‘9’ 
The first data content 
‘1’   
END 
CR 
‘3’    LF 
‘8’       
‘8’       
The second data 
content 
‘0’       
‘F’       
‘A’       
‘0’       
LRC Check 
‘9’       
‘B’       
END 
CR       
LF       
RTU mode: 
Command Message:    Response Message: 
ADR  01H    ADR  01H 
CMD  10H    CMD 1  10H 
Target register 
04H   
Target register 
04H 
00H    00H 
Number of register 
(Count by word) 
00H    Number of register 
(Count by word) 
00H 
02H    02H 
Quantity of data (byte)  04    CRC Check Low  40H 
The first data content 
13H    CRC Check High  F8H 
88H       
The second data 
content 
0FH       
A0H       
CRC Check Low  ‘9’       
CRC Check High  ‘A’       
Check sum 
ASCII mode:   
LRC (Longitudinal Redundancy Check) is calculated by summing up the values of the bytes from 
ADR1  to  last  data  character  then  calculating  the  hexadecimal  representation  of  the 
2’s-complement negation of the sum. 
For example,   
01H+03H+21H+02H+00H+02H=29H, the 2’s-complement negation of 29H is D7H.