Chapter 12 Description of Parameter SettingsCP2000 
 
 
12.1-09-8 
4.  Address list 
AC motor drive parameters (GGxx) 
Modbus 
address 
Function 
GGnnH 
GG is the parameter group, nn is the parameter number; for example, the address of 
Pr.04-10 is 040AH. 
Control command (20xx) 
Modbus 
address 
R/W  Function 
2000H  RW 
bit1–0 
00B: No function 
01B: Stop 
10B: Run 
11B: JOG + RUN 
bit3–2  Reserved 
bit5–4 
00B: No function 
01B: FWD 
10B: REV 
11B: Change direction 
bit7–6 
00B: 1
st
 acceleration / deceleration 
01B: 2
nd
 acceleration / deceleration 
10B: 3
rd
 acceleration / deceleration 
11B: 4
th
 acceleration / deceleration 
bit11–8 
0000B: Master speed 
0001B: 1
st
 Step speed frequency 
0010B: 2
nd
 Step speed frequency 
0011B: 3
rd
 Step speed frequency 
0100B: 4
th
 Step speed frequency 
0101B: 5
th
 Step speed frequency 
0110B: 6
th
 Step speed frequency 
0111B: 7
th
 Step speed frequency 
1000B: 8
th
 Step speed frequency 
1001B: 9
th
 Step speed frequency 
1010B: 10
th
 Step speed frequency 
1011B: 11
th
 Step speed frequency 
1100B: 12
th
 Step speed frequency 
1101B: 13
th
 Step speed frequency 
1110B: 14
th
 Step speed frequency 
1111B: 15
th
 Step speed frequency 
bit12 
1: Enable bit06
–11 function 
bit15 
Reserved 
2001H  RW  Frequency command (XXX.XX Hz) 
2002H  RW 
bit0  1: E.F. ON 
bit1 
1: Reset 
bit2  1: Base block (B.B) ON 
bit15–3  Reserved 
Status monitor read only (21xx) 
Modbus 
address 
R/W  Function 
2100H  R 
High byte: Warn Code 
Low Byte: Error Code