Chapter 14 Fault Codes and DescriptionsCP2000 
 
14-41
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
77 
 
STO Loss 2 (STL2)  STO2–SCM2 internal loop detection error 
Action and Reset 
Action level  Hardware detection 
Action time  Immediately act 
Fault treatment parameter  N/A 
Reset method  Hardware failure, and cannot reset. Cycle the power. 
Reset condition  N/A 
Record  Yes 
Cause  Corrective Actions 
STO2 and SCM2 short circuit lines 
are not connected 
Connect the short circuit lines 
Hardware failure 
After you make sure all the wiring is correct, if STL2 fault still exists after cycling 
the power, please return to the factory for repair.   
Poor connection of the IO card 
Check if the PIN of IO card is broken? 
Check if the IO card connects to the control board correctly, and if the screws 
are tightened well? 
The IO card does not match the 
version of the control board 
Contact local agent or Delta 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
78 
STO Loss 3 (STL3) 
STO1–SCM1 and STO2–SCM2 internal loop detection 
error 
Action and Reset 
Action level  Hardware detection 
Action time  Immediately act 
Fault treatment parameter  N/A 
Reset method  Hardware failure, and cannot reset. Cycle the power. 
Reset condition  N/A 
Record  Yes 
Cause  Corrective Actions 
STO1 and SCM1, or STO2 and 
SCM2 short circuit lines are not 
connected 
Re-connect the short circuit lines 
Hardware failure 
After you make sure all the wiring is correct, if STL3 fault still exists after cycling 
the power, please return to the factory for repair.   
Poor connection of the IO card 
Check if the PIN of IO card is broken? 
Check if the IO card connects to the control board correctly, and if the screws 
are tightened well? 
The IO card does not match the 
version of the control board 
Contact local agent or Delta